Having trouble reading this e-mail? View it on our website

AlpineViews

May 2010
Written by Jonathan Hill

Safer electrical inspections webinar

Last week, we ran our first webinar of the year, which discussed ways in which engineers can carry out quicker and safer infrared inspections of switchgear, and the benefits of using Thermographic Inspection Windows.

We'd like to thank David Furley for putting together such an informative talk, as well as everyone who attended and asked questions. If you were unable to join in, though, then you can now watch it again on our website.

We're also in the midst of planning some more webinars, so please continue to send us your feedback so that we can cover all subjects of interest.

Level 1 Thermography Courses

Earlier in the year, we carried out an on-site Level 1 Thermography Course (in conjunction with Flir Systems) at a British Energy power station up in the north west.

It occurred to me at the time that, while we always mention our ultrasound training courses, we very rarely highlight upcoming infrared courses, even though they always prove to be popular and well attended.

With that in mind, here's the list of dates and locations currently scheduled for the second half of 2010...

  • June 21-25  -  Milton Keynes
  • July 19-23  -  Cardiff
  • September 13-17  -  Ireland
  • September 20-24  -  Kent
  • October 11-15  -  Manchester
  • November 15-19  -  Milton Keynes
  • December 06-10  -  Kent

Please visit our website for an overview of what this comprehensive five-day thermography course covers. Alternatively, you can send me an e-mail if you'd like to book someone along on one of the above dates.

Time for a quick teaser... If you've met our Micky Jackson, can you spot him in the training photo above? Answers on a postcard!

Contribution from RWE npower

RWE npower operate a number of coal, oil and gas-fired power stations, and supply gas and electricity to both homes and businesses. Tom Maund, who is a performance engineer in the Performance Development group, kindly wrote the following piece, which highlights the success they've had using the PHD-4 helium leak detector.

"Over the past 18 months, engineers working for RWE npower have carried out a comprehensive series of tests to ascertain the level of condenser air ingress across its portfolio of Coal, Oil, Combined Cycle Gas Turbine (CCGT) and Cogen sites."

"Condenser air ingress has a detrimental effect on the thermal performance of condensers, and can also be attributed to corrosion and other mechanical failures within a condenser. Deviations in condenser backpressure can be very costly, and a typical 500 MW coal fired unit running at 5 mb above target would incur significant additional running costs."

"Fundamental in RWE's approach to identifying source sites for air ingress has been the PHD-4. It has proved both reliable and robust, and several units have been bought to allow greater flexibility for sites to carry out surveys. Helium is sprayed around any areas on a generating unit that may be subject to sub atmospheric or vacuum conditions, and a sample gas is measured at the main air extraction pump exhaust. The helium concentration indicated by the PHD-4 in the sample gas is representative (if not wholly accurate) of the level of air ingress at the spray site."

"Initial issues in the use of the PHD-4 were that it had to be placed near to the air extraction point and watched continuously for any indication of helium being detected."

"As well as this, most units are very noisy, large and spread over several levels - communication between personnel at the spray site and at the sample extraction point was difficult and prolonged the testing period over several days, utilising 3 engineers to carry out a full survey."

"Developments over a period of time have enabled engineers to provide a wireless interface between the PHD-4 and a laptop, which enables operators to get a real-time indication of helium detection at the spray site, which vastly decreases the amount of testing time. Where immediate repairs can be carried out, re-testing can be done to quickly assess their effectiveness."

"In addition to the PHD-4, engineers also make use of the Ultraprobe to carry out vacuum leaks surveys (where access permits) on areas of plant such as Low Pressure Turbine Hood joints that lend themselves to rapid testing. Any suspect areas can then be easily and quickly checked using helium detection."

"Both instruments form part of a suite of tools and complimentary equipment used by RWE engineers known as COOLAIRS (Condenser On Off Load Air Ingress Reduction System)."

"In the 18 months, RWE engineers have had a great deal of success in identifying and reducing the level of condenser air ingress across many sites, achieving significant savings directly attributable to the work done with the PHD-4 and Ultraprobe. In addition, the PHD-4 has been used with a lot of success to detect air ingress on some unit main oil tanks that operate slightly sub atmospheric conditions."

Contact us

It is always good to receive feedback on any products that we have sold or rented. If you have a success story or tip that you would like to share with other readers in a future newsletter, then please get in touch using the contact details below...

Telephone: 01424 437000
Fax: 01424 722502
E-mail: info@alpine-components.co.uk
Website: www.alpine-components.co.uk


© 2010 Alpine Components Ltd
14-15 Oban Road, St. Leonards-on-Sea, East Sussex, TN37 7DX

Unsubscribe from our newsletters